Greenrich COMMUNICATION WITH SUNSYNK INVERTER (5KW, 8KW & 12KW)
-
-
-
- COMMUNICATION WITH SUNSYNK INVERTER (5KW, 8KW ,12KW).
- Connect the battery terminals securely from your batteries to the inverter. Positive (+) from your battery to positive (+) terminal on your inverter, negative (-) from your battery to negative terminal (-) on your inverter
- If you are using 2 or more batteries connect the positive (+) of the first battery to the positive (+) of the next battery, similarly, connect the negative (-) of the first battery to the negative (-) of the second battery. When connecting your battery to the inverter connect your red (+) cable to the positive terminal of the first battery and your black (-) cable to the negative terminal of your last battery. Remember to connect the communication cable between your batteries.
- For communication using CAN Port use NORMAL RJ45 cable with normal pin – pin connections.
Connect the communication cable on the CAN PORT on the battery (next to RS 485 port) to the inverters BMS CAN port.
LCD SETTINGS ON THE INVERTER
- First turn on the battery and do all settings on the inverter BEFORE switching on AC INPUT and PV INPUT .
- On your main screen CLICK the settings icon on the RIGHT top
Corner
- Click battery setting
- Select battery type to lithium and then enter battery parameters. When inputting these values uses the down and up keys on the inverter(hard keys).
- battery capacity – 72ah
- maximum charging current – 100A
iii. maximum discharge current – 100A
NB: When using 2 or more batteries you need to MULTIPLY the above values with the number of batteries you are connecting.
- When using CAN PORT ( both on battery and inverter) please select CAN.
- After entering the above battery parameters press OK and ESC to the main screen.
- To verify that there is communication between inverter and the battery CLICK setting icon on the top right corner and click LI - BMS icon, if there is communication you should be able to see the battery information/ parameters.
-
-